[Skip to main content]
Buderus logo

Buderus commercial and domestic boilers

[GB 312 480kW]

Dimensions

Parameter Value
Length, LK 1410mm
Length, LG 2620mm
Length, LG1 2247mm
Width, BG 2139mm
Net weight 600kg
Installation dimensions, K 431mm
Installation dimensions, M 663mm
Installation dimensions, N 369mm
Installation dimensions, O 619mm
Installation dimensions, R 982mm
Installation dimensions, S 454mm
Installation dimensions, S1 157mm
Installation dimensions, U 259mm
Flue gas connection, ØDAA 250DN
Flue gas connection, HAA 2135mm
Flue gas connection, HAA1 1732mm
Flue gas connection, A2 488mm
Boiler flow connection, ØVK 100DN
Boiler flow connection, HVK 1299mm
Boiler return connection, Ø RK 100DN
Boiler return connection, HRK 330mm
Distance, BZ 936mm
Air sealed, ØRLU 110DN
Air sealed, HRLU 1018mm
Gas connection, ØGAS R1½"
Gas connection, HGAS 1143mm
Gas connection, A1 374mm

Technical Parameters

Parameter Value
Output 480kW
Nominal heat output at 80/60 °C, Full load 450kW
Nominal heat output at 80/60 °C, Part load 66kW
Nominal heat output at 50/30 °C, Full load 480kW
Nominal heat output at 50/30 °C, Part load 75kW
Rated heat input, Part load 69kW
Rated heat input, Full load 464kW
Max working pressure 4bar
Max flow temperature 80°C
Electrical power consumption, full load 540W
Electrical power consumption, part load 50W
Gas pressure 17 - 24 mbar
Water content 54l
Electrical ingress protection IP 40
CE certification, product ID no. CE 0085BP5508
Pressure at flue outlet 100Pa
Water flow resistance, ΔT 20K 89mbar
Safety temperature letter 100°C
Electrical connection 230VAC 50Hz
Flue gas mass flow rate at 50/30 °C, Full load 212g/s
Flue gas mass flow rate at 50/30 °C, Part load 30.2g/s
Flue gas mass flow rate at 80/60 °C, Full load 210g/s
Flue gas mass flow rate at 80/60 °C, Part load 32.4g/s
CO2 content, Full load 9.1%
CO2 content, Part load 9.3%
Sound emission level, Full load 58dB(A)
Sound emission level, Part load 40dB(A)
Min flue gas temperature at 80/60 °C, Full load 74°C
Min flue gas temperature at 80/60 °C, Part load 55°C
Min flue gas temperature at 50/30 °C, Part load 31°C
Min flue gas temperature at 50/30 °C, Full load 55°C

Return to GB 312 Cascades

 