Dimensions

Parameter Value
Length, L 4143mm
Length, LK 1974mm
Length, LWT1 1120mm
Length, LWT2 875mm
Width HE, BWT 870mm
Height max with controls 2092mm
Height, HWT 2027mm
Net weight of boiler and heat exchanger 3127kg
Flue gas connection, HAA 334mm
Combustion chamber, Length 1695mm
Combustion chamber, Ø 680mm
Burner door, Depth 145mm
Boiler flow connection, Ø VK Connection flange can be ordered as reduced to DN 150, DN 125 or DN 100
Boiler flow connection, HVK 1640DN
Boiler return connection, Ø RK Connection flange can be ordered as reduced to DN 150, DN 125 or DN 100
Boiler return connection, HRK 1365DN
Heat exchanger flow, Ø VWT 125DN
Heat exchanger flow, HVWT 1487mm
Heat exchange return, Ø RWT 125DN
Heat exchange return, HRWT 483mm
Safety outlet from the heat exchanger 1542mm
Adjustable feet, LPWT 694mm
Adjustable feet, BPWT 694mm
Condensate drain, HAKO 160mm
Drain, HEL 431mm

Technical Parameters

Parameter Value
Output 745kW
Nominal heat output at 75/60 °C 693kW
Nominal heat output at 55/30 °C 745kW
Max working pressure 6bar
Max flow temperature 120°C
Water content 982l
Gas content 1540l
CE certification, product ID no. CE-0085 AU 0451
Pressure at flue outlet 50Pa
Heat transfer rating of the heat exchanger (at system temperature) at 55/30 °C 79.8kW
Heat transfer rating of the heat exchanger (at system temperature) at 75/60 °C 32.6kW
Type approval number, Boiler 06-226-713
Type approval number, Heat exchanger 06-610-016
Efficiency (NCV) 107%
Rated heat input at 55/30 °C 714kW
Rated heat input at 75/60 °C 714kW
Pressure loss combustion side 5mbar
Flue gas temperature at 55/30 °C 51°C
Flue gas temperature at 75/60 °C 75°C
Flue gas mass flow rate at 55/30 °C 0.301kg/s
Flue gas mass flow rate at 75/60 °C 0.304kg/s
CO2 content, natural gas G20 at 55/30 °C 10%
CO2 content, natural gas G20 at 75/60 °C 10%