[GB 312 200kW]
Dimensions
| Parameter | Value |
|---|---|
| Height max incl. controls | 1532mm |
| Width,TK | 1202mm |
| Width for access | 612mm |
| Depth | 625mm |
| Net weight | 265kg |
| Flue gas connection, Ø DAA (internal) | 200DN |
| Flue gas connection, HAA | 495mm |
| Flue gas connection, A2 | 436mm |
| Boiler flow connection, Ø VK | DN 65 |
| Boiler flow connection, HVK | 1300mm |
| Boiler flow connection | 215mm |
| Boiler return connection, Ø RK | DN 65 |
| Boiler return connection, HRK | 615mm |
| Boiler return connection, A3 | 270mm |
| Safety valve, Ø ST | Rp1½mm |
| Air sealed, Ø RLU | 110DN |
| Air sealed, HRLU | 1029mm |
| Air sealed, A1 | 373mm |
| Gas connection, Ø GAS | R1½ |
| Gas connection, HGAS | 1143mm |
| Gas connection, A1 | 269mm |
Technical Parameters
| Parameter | Value |
|---|---|
| Output | 200kW |
| Nominal heat output at 80/60 °C, Full load | 187kW |
| Nominal heat output at 80/60 °C, Part load | 55kW |
| Nominal heat output at 50/30 °C, Full load | 200kW |
| Nominal heat output at 50/30 °C, Part load | 62kW |
| Rated heat input, Part load | 57kW |
| Rated heat input, Full load | 193kW |
| Max working pressure | 4bar |
| Max flow temperature | 80°C |
| Electrical power consumption, full load | 230W |
| Electrical power consumption, part load | 50W |
| Gas pressure | 17-24 mbar |
| Water content | 24l |
| Electrical ingress protection | IP 40 |
| CE certification, product ID no. | CE 0085BP5508 |
| Pressure at flue outlet | 100Pa |
| Water flow resistance, ΔT 20K | 90mbar |
| Safety temperature letter | 100°C |
| Electrical connection | 230VAC 50Hz |
| Efficiency (NCV) | 108% |
| Flue gas temperature at 50/30 °C, Full load | 55°C |
| Flue gas temperature at 50/30 °C, Part load | 33°C |
| Flue gas temperature at 80/60 °C, Full load | 76°C |
| Flue gas temperature at 80/60 °C, Part load | 58°C |
| Flue gas mass flow rate at 50/30 °C, Full load | 87.8g/s |
| Flue gas mass flow rate at 50/30 °C, Part load | 25.1g/s |
| Flue gas mass flow rate at 80/60 °C, Full load | 88g/s |
| Flue gas mass flow rate at 80/60 °C, Part load | 26.7g/s |
| CO2 content, Full load | 9.1% |
| CO2 content, Part load | 9.3% |
| Sound emission level, Full load | 55dB(A) |
| Sound emission level, Part load | 40dB(A) |