[Skip to main content]
Buderus logo

Buderus commercial and domestic boilers

[SB 825L 5200kW]

Dimensions

Parameter Value
Length, L 5390mm
Length, LK 4380mm
Width, B 1924mm
Width, BWT1 1564mm
Width, BWT2 835mm
Height, HF 2200mm
Height, HK 2210mm
Height, HWT 970mm
Operating weight 6 bar 13.0t
Operating weight 10 bar 13.9t
Shipping weight 6 bar 8.7t
Shipping weight 10 bar 9.6t
Flue gas connection, HAA 1330mm
heat exchanger, Ø AA 630DN
Combustion chamber, Length 4106mm
Combustion chamber, Ø 1012mm
Burner door, Depth 257mm
Burner door, HB 1100mm
Base frame, LGR 3920mm
Base frame, BGR 1510mm
Base frame, U-Profile 220mm
Boiler flow / return connection 150DN
Heat exchanger flow, HVWT 1616mm
Heat exchanger return, HRWT 1044mm
Drain, ELK 32DN
Drain, ELA ¾"DN
Flange VK/RK/VSL, ∆t = 15K 250DN
Flange VK/RK/VSL, ∆t = 20K 200DN
Flange VK/RK/VSL, ∆t = 30K 200DN
Flange VK/RK/VSL, ∆t = 40K 150DN
Distance, A1 2770mm
Distance, A2 800mm
Distance, A3 750mm
Distance, A4 -

Technical Parameters

Parameter Value
Max working pressure 6bar to 10bar
Flue gas temperature at 60 °C 124°C
Flue gas temperature at 30 °C 110°C
Max flow temperature 110°C
Water flow resistance 250mbar
Flow rate crossing the external heat exchanger 156m3/h
Nominal output heat exchanger at 60 °C 162kW
Nominal output heat exchanger at 30 °C 413kW
Max nominal heat output boiler 5200kW
Water content 4.3m3
Flue gas resistance 15.2mbar
Gas content 5.94m3
CE certification, product ID no. CE-0085BO0397
Pressure at flue outlet 0 (50Pa burner dependent
Efficiency (NCV) 104%
CO2 content, Gas 10.5%

Return to SB 825L

 