[Skip to main content]
Buderus logo

Buderus commercial and domestic boilers

[G 215 78kW]

Dimensions

Parameter Value
Number of sections 6
Length, LK 920mm
Width 600mm
Width for access 460mm
Height 1111mm
Height max incl controls 1126mm
Transportation, Boiler section Width 460/Height 820/Depth 150mm
Transportation, Boiler block Width 460/Height 820/Depth LKmm
Net weight 317kg
Combustion chamber, LF 788mm
Combustion chamber, Ø 337mm
Burner door, Depth 95mm
Burner door, Ø DB 110mm
Burner door, Ø Hole circle 150mm
Adjusted feet, FL 695mm

Technical Parameters

Parameter Value
Output 78kW
Max working pressure 4bar
Max flow temperature 120°C
Rated heat input 63.3kW - 85.1kW
Water content 85l
Pressure at flue outlet 0Pa
Flue gas resistance 0.25mbar - 0.46mbar
Gas content 101.4l
Type approval number Z-FDK-MUC-00-318-302-24
CE certification, product ID no. CE 00 85 AS 0368
Nominal heat output 59kW - 78kW
Flue gas temperature 160°C - 198°C
Efficiency (NCV) 95%

Return to G 215

 