Dimensions
| Parameter | Value |
|---|---|
| Number of sections | 7 |
| Length, LK | 1290mm |
| Height max incl controls | 1266mm |
| Width | 880mm |
| Width for access assembled | 712mm |
| Net weight | 719kg |
| Combustion chamber, Length | 1110mm |
| Combustion chamber, Ø | 400mm |
| Burner door, Depth | 125mm |
| Boiler flow connection, Ø VK | Connection flange can be ordered as reduced to DN 65, DN 50 or DN 40 |
| Boiler return connection, Ø RK | Connection flange can be ordered as reduced to DN 65, DN 50 or DN 40 |
Technical Parameters
| Parameter | Value |
|---|---|
| Output | 170kW |
| Max flow temperature | 120°C |
| Rated heat input | 151kW - 183.4kW |
| Water content | 199l |
| Pressure at flue outlet | 0Pa |
| Flue gas resistance | 0.71mbar - 1.3mbar |
| Gas content | 215l |
| CE certification, product ID no. | CE-461 AS 255 |
| Nominal heat output | 141kW - 170kW |
| Max working pressure (gauge) | 6bar |
| Flue gas temperature | 162°C - 180°C |
| Type approval no. | 06-226-683 |
| Efficiency (NCV) | 96% |
| Flue gas mass flow rate, Oil full load | 0.0641kg/s - 0.0779kg/s |
| Flue gas mass flow rate, Oil part load 60% | 0.0458kg/s |
| Flue gas mass flow rate, Gas part load 60% | 0.046kg/s |
| Flue gas mass flow rate, Gas full load | 0.0643kg/s - 0.0781kg/s |
| CO2 content, Gas | 10% |
| CO2 content, Oil | 13% |
Return to GE 315