Dimensions

Parameter Value
Number of sections 8
Length, LK 1450mm
Height max incl controls 1266mm
Width 880mm
Width for access assembled 712mm
Net weight 807kg
Combustion chamber, Length 1270mm
Combustion chamber, Ø 400mm
Burner door, Depth 125mm
Boiler flow connection, Ø VK Connection flange can be ordered as reduced to DN 65, DN 50 or DN 40
Boiler return connection, Ø RK Connection flange can be ordered as reduced to DN 65, DN 50 or DN 40

Technical Parameters

Parameter Value
Output 200kW
Max flow temperature 120°C
Rated heat input 183.1kW - 215.1kW
Water content 227l
Pressure at flue outlet 0Pa
Flue gas resistance 1.34mbar - 1.78mbar
Gas content 249l
CE certification, product ID no. CE-461 AS 255
Nominal heat output 171kW - 200kW
Max working pressure (gauge) 6bar
Flue gas temperature 158°C - 176°C
Type approval no. 06-226-683
Efficiency (NCV) 96%
Flue gas mass flow rate, Oil full load 0.0777kg/s - 0.0913kg/s
Flue gas mass flow rate, Oil part load 60% 0.0539kg/s
Flue gas mass flow rate, Gas part load 60% 0.0541kg/s
Flue gas mass flow rate, Gas full load 0.0780kg/s - 0.0916kg/s
CO2 content, Gas 10%
CO2 content, Oil 13%

Return to GE 315

 