[Skip to main content]
Buderus logo

Buderus commercial and domestic boilers

[GE 315 230kW]

Dimensions

Parameter Value
Number of sections 9
Length, LK 1610mm
Height max incl controls 1266mm
Width 880mm
Width for access assembled 712mm
Net weight 895kg
Combustion chamber, Length 1430mm
Combustion chamber, Ø 400mm
Burner door, Depth 125mm
Boiler flow connection, Ø VK Connection flange can be ordered as reduced to DN 65, DN 50 or DN 40
Boiler return connection, Ø RK Connection flange can be ordered as reduced to DN 65, DN 50 or DN 40

Technical Parameters

Parameter Value
Output 230kW
Max flow temperature 120°C
Rated heat input 215.2kW - 247.9kW
Water content 255l
Pressure at flue outlet 0Pa
Flue gas resistance 1.32mbar -1.77mbar
Gas content 263l
CE certification, product ID no. CE-461 AS 255
Nominal heat output 201kW - 230kW
Max working pressure (gauge) 6bar
Flue gas temperature 168°C - 190°C
Type approval no. 06-226-683
Efficiency (NCV) 96%
Flue gas mass flow rate, Oil full load 0.913kg/s - 0.1052kg/s
Flue gas mass flow rate, Oil part load 60% 0.062kg/s
Flue gas mass flow rate, Gas part load 60% 0.0622kg/s
Flue gas mass flow rate, Gas full load 0.0917kg/s - 0.1056kg/s
CO2 content, Gas 10%
CO2 content, Oil 13%

Return to GE 315

 