[Skip to main content]
Buderus logo

Buderus commercial and domestic boilers

[GE 515 455kW]

Dimensions

Parameter Value
Number of sections 11
Length, L 2260mm
Length, LK 2040mm
Height max incl controls 1556mm
Width 980mm
Net weight 1900kg
Combustion chamber, Length 1845mm
Combustion chamber, Ø 515mm
Burner door, Depth 142mm
Boiler flow connection, Ø VK Connecting flange as ordered, reduced to DN 100, DN 80 or DN 65
Boiler return connection, Ø RK Connecting flange as ordered, reduced to DN 100, DN 80 or DN 65

Technical Parameters

Parameter Value
Output 455kW
Max flow temperature 120°C
Rated heat input 428.4kW - 489.2kW
Water content 402l
Pressure at flue outlet 0Pa
Flue gas resistance 2.5mbar - 3.3mbar
Gas content 681l
CE certification, product ID no. CE-0461 AR 6154
Nominal heat output 401kW - 455kW
Max working pressure (gauge) 6bar
Type approval no. 06-226-640
Flue gas temperature, 60% part load 130°C
Flue gas temperature, Full load 159°C - 172°C
Efficiency (NCV) 96%
Flue gas mass flow rate, Oil full load 0.182kg/s - 0.208kg/s
Flue gas mass flow rate, Oil part load 60% 0.123kg/s
Flue gas mass flow rate, Gas part load 60% 0.123kg/s
Flue gas mass flow rate, Gas full load 0.183kg/s - 0.208kg/s
CO2 content, Gas 10%
CO2 content, Oil 13%

Return to GE 515

 
Intelligent Heating SolutionsBosch Thermotechnology Ltd.