Parameter Value
Number of sections 16
Length, L 3116mm
Length, LK 2994mm
Height max incl controls 1826mm
Width 1281mm
Net weight 4147kg
Combustion chamber, Length 2715mm
Combustion chamber, Ø 680mm
Burner door, Depth 145mm
Boiler flow connection, Ø VK Connection flange can be ordered as reduced to DN 150, DN 125 or DN 100
Boiler return connection, Ø RK Connection flange can be ordered as reduced to DN 150, DN 125 or DN 100

Technical Parameters

Parameter Value
Output 1200kW
Max flow temperature 120°C
Rated heat input 1188kW - 1297kW
Water content 981l
Pressure at flue outlet 0Pa
Flue gas resistance 5.8mbar
Gas content 1657l
CE certification, product ID no. CE-461 AS 255
Nominal heat output 1111kW - 1200kW
Max working pressure (gauge) 6bar
Type approval no. 06-226-713
Flue gas temperature, 60% part load 140°C
Flue gas temperature, Full load 170°C - 180°C
Efficiency (NCV) 96%
Flue gas mass flow rate, Oil full load 0.5043kg/s - 0.5505kg/s
Flue gas mass flow rate, Oil part load 60% 0.3234kg/s
Flue gas mass flow rate, Gas part load 60% 0.3246kg/s
Flue gas mass flow rate, Gas full load 0.5061kg/s - 0.5525kg/s
CO2 content, Gas 10%
CO2 content, Oil 13%