Dimensions

Parameter Value
Number of sections 13
Length, L 2606mm
Length, LK 2484mm
Height max incl controls 1826mm
Width 1281mm
Net weight 3475kg
Combustion chamber, Length 2205mm
Combustion chamber, Ø 680mm
Burner door, Depth 145mm
Boiler flow connection, Ø VK Connection flange can be ordered as reduced to DN 150, DN 125 or DN 100
Boiler return connection, Ø RK Connection flange can be ordered as reduced to DN 150, DN 125 or DN 100

Technical Parameters

Parameter Value
Output 920kW
Max flow temperature 120°C
Rated heat input 878.1kW - 994.6kW
Water content 801l
Pressure at flue outlet 0Pa
Flue gas resistance 4.1mbar
Gas content 1342l
CE certification, product ID no. CE-461 AS 255
Nominal heat output 821kW - 920kW
Max working pressure (gauge) 6bar
Type approval no. 06-226-713
Flue gas temperature, 60% part load 140°C
Flue gas temperature, Full load 170°C - 180°C
Efficiency (NCV) 96%
Flue gas mass flow rate, Oil full load 0.3727kg/s - 0.4222kg/s
Flue gas mass flow rate, Oil part load 60% 0.2479kg/s
Flue gas mass flow rate, Gas part load 60% 0.2488kg/s
Flue gas mass flow rate, Gas full load 0.3741kg/s - 0.4237kg/s
CO2 content, Gas 10%
CO2 content, Oil 13%

Return to GE 615

 