[Skip to main content]
Buderus logo

Buderus commercial and domestic boilers

[S 825L 3700kW]

Dimensions

Parameter Value
Length, L 4075mm
Length, LK 3820mm
Width, B 1724mm
Height, HF 2015mm
Height, HK 2015mm
Operating weight 6 bar 8.8t
Operating weight 10 bar 9.5t
Shipping weight 6 bar 5.7t
Shipping weight 10 bar 6.5t
Flue gas connection, Ø AA 505mm
Flue gas connection, HAA 1490mm
Combustion chamber, Length 3553mm
Combustion chamber, Ø 901mm
Burner door, Depth 190mm
Burner door, HB 1000mm
Base frame, LGR 3410mm
Base frame, BGR 1150mm
Base frame, U-Profile 200mm
Drain, ELK 32DN
Drain, ELA ¾"DN
Flange VK/RK/VSL, ∆t = 15K 200DN
Flange VK/RK/VSL, ∆t = 20K 200DN
Flange VK/RK/VSL, ∆t = 30K 150DN
Flange VK/RK/VSL, ∆t = 40K 125DN
Distance, A1 2490mm
Distance, A2 600mm
Distance, A3 800mm
Distance, A4 -

Technical Parameters

Parameter Value
Max working pressure 6bar to 10bar
Max flow temperature 110°C
Water content 3m3
Pressure at flue outlet 0Pa
Gas content 3.67m3
CE certification, product ID no. CE-0085BO0396
Nominal heat output 3700kW
CO2 content, Gas 10.5%
CO2 content, Oil 13.5%

Return to S 825L

 
Intelligent Heating SolutionsBosch Thermotechnology Ltd.