[Skip to main content]
Buderus logo

Buderus commercial and domestic boilers

[S 825L 4200kW]

Dimensions

Parameter Value
Length, L 4570mm
Length, LK 4250mm
Width, B 1824mm
Height, HF 2115mm
Height, HK 2115mm
Operating weight 6 bar 11.1t
Operating weight 10 bar 11.8t
Shipping weight 6 bar 7.3t
Shipping weight 10 bar 8t
Flue gas connection, Ø AA 505mm
Flue gas connection, HAA 1500mm
Combustion chamber, Length 3987mm
Combustion chamber, Ø 932mm
Burner door, Depth 257mm
Burner door, HB 1050mm
Base frame, LGR 3920mm
Base frame, BGR 1260mm
Base frame, U-Profile 220mm
Drain, ELK 32DN
Drain, ELA ¾"DN
Flange VK/RK/VSL, ∆t = 15K 200DN
Flange VK/RK/VSL, ∆t = 20K 200DN
Flange VK/RK/VSL, ∆t = 30K 150DN
Flange VK/RK/VSL, ∆t = 40K 125DN
Distance, A1 2870mm
Distance, A2 600mm
Distance, A3 650mm
Distance, A4 -

Technical Parameters

Parameter Value
Max working pressure 6bar to 10bar
Max flow temperature 110°C
Water content 3.8m3
Pressure at flue outlet 0Pa
Gas content 4.61m3
CE certification, product ID no. CE-0085BO0396
Nominal heat output 4200kW
CO2 content, Gas 10.5%
CO2 content, Oil 13.5%

Return to S 825L

 
Intelligent Heating SolutionsBosch Thermotechnology Ltd.